AB Rockwell PLC5 and SLC Connector
Devices Using DF1 Protocol (SLC, PLC5)
- Name: DF1Ethernet
- Version 1.9.1.1
- Protocol: DF1
- Interface: TCP/IP
- Runtime: .NET 2.0 (Multiplatform)
- Configuration:
- Devices / Protocols
Points Configuration
Point Address Syntax
The syntax for the ControlLogix communication points is: <File Type><Element Number> : <Address>
- File Type: identifies the Operand.
- File Number: number reference for the File Type
- Element Number: number address for that file in the PLC.
The valid values for File Type are:
DF1Ethernet Driver File Types | ||||||
|---|---|---|---|---|---|---|
File | Read | Write | Bit Read | Bit Write | Data Type | Address size |
N Integer | Yes | Yes | Yes | Yes | Word | 2 bytes |
B Binary | Yes | Yes | Yes | Yes | Word | 2 bytes |
F FloatPoint | Yes | Yes | Yes | Yes | Single | 4 bytes |
O OutputLogical | Yes | Yes | Yes | Yes | Word | 2 bytes |
I InputLogical | Yes | - | Yes | - | Word | 2 bytes |